piwik image

LUT-ELI-3PH Lutron®
Send Print
  1. pin-int

LUTLUTELI3PH

Lutron® LUT-ELI-3PH Emergency Lighting Interface, 100/347 VAC, 30 mA

  • Manufacturers: Lutron Electronics
  • Brand Name: Lutron®
  • BPN: LUTLUTELI3PH
  • MPN: LUT-ELI-3PH
  • UPC:027557067058
  • Min. Order Qty: 1
  • Qty. Interval: 1
  • Available at this location: loading -- Locations

The LUT-ELI-3PH is a device that works with Lutron® lighting controls to provide an emergency lighting solution. The device is capable of sensing normal (non-essential) line voltage power and accepting an output from a fire alarm control panel (FACP). Upon loss of normal power or receiving a signal from the FACP, the LUT-ELI-3PH will send a signal to the compatible Lutron® controls ) to which it is connected. This signal will cause the controls to enter the emergency lighting mode and any lights controlled will go to the emergency light level setting.

Lutron® Emergency Lighting Interface, Series: LUT-ELI, 100/347 VAC, 30 mA, Surface Mounting, 0 to 40 deg C, 7-3/4 in H x 5 in W x 2-1/2 in D Dimensions

Amperage Rating      :      30 mA
Dimensions      :      7-3/4 in H x 5 in W x 2-1/2 in D
Mounting Type      :      Surface
Series      :      LUT-ELI
Temperature Rating      :      0 to 40 deg C
Voltage Rating      :      100/347 VAC
  • Compatible Lutron controls GP, LP, LCP, XP, XPS, CCP, CXP, HS and HomeWorks® rough-in panels, Energi Savr Node™ units, GRAFIK Eye® QS units, Quantum® lighting management hubs with EcoSystem® bus supplies
  • Requires a 24 VAC power feed from a source on normal/emergency (essential) power for unit to operate
  • Status light indicates the phase status, status light ON is normal mode, OFF is emergency mode
  • A test button is provided to perform a functional test of the system by simulating an emergency situation
  • Accepts a maintained dry contact closure from an FACP to actuate the emergency mode
  • Senses line voltage from 100/347 VAC
  • 50/60 Hz frequency
  • Relative humidity less than 90% non-condensing
  • pdfSpecification Sheet https://externalassets.unilogcorp.com/ASSETS/DOCUMENTS/ITEMS/EN/Lutron_LUT_ELI_3PH_Data_Sheet.pdf